ADM-4162D 12 way switch quantity acquisition DI/DO 4 road relay output control module MODBUS RS485 communication

USD 36.31USD 39.90

ADM-4162D 12 way switch quantity acquisition DI/DO 4 road relay output control module MODBUS RS485 communication

Description
ADM-4162D is a 12 Channel digital input and 4 Channel (normally open) relay
output module, which is used in industrial field signal acquisition, monitoring and control. Support 12 channel isolation digital input and 4 channel A type relay output.RS-485 communication interface, support the MODBUS RTU protocol, can connect configuration software, PLC, DCS industrial control touch screen.

 

Product specification
Digital input:
1. Input channel: 12 Channel dry contact or level signal
2. Input polarity: co - negative or co - positive (automatic adaptation)
3. Input range: high level (1):7.5V - 30V, low level (0): 0V - 1V
4. Sampling rate: 1000Hz
5. Isolation voltage: 1500V
6. Input counter: 16 bit (0~65535), input frequency less than 200HZ
Digital output:
1. Output channel: 4 channel A type (often open) relay output
2. Load voltage: maximum DC24V
3. Load current: 1A
 
Communication interface:
1. Communication protocol: MODBUS-RTU
2. Interface type: RS-485 interface
3. Interface protection: 15KV ESD protection, 1500V isolation protection
4. Baud rate: 1200/2400/4800/9600/19200/38400/57600/115200
5. Parity:No, even, odd
6. Default: 9600, N, 8, 1 (modifiable)
 
System parameter:
1. Module size: 104mm x 72mm x 26mm
2. Installation: 35mm din rail installation
3. Environment: temperature: -20~70 C humidity: 0-95%, not condensing
4. Power supply: DC9~30V is less than 3W
 
LED directive definition
1. POWER: power status indication, "bright" power supply is normal
2. COMM: RS-485 communication indicates that "flash" is sending and receiving data
3. DI0~DI11: digital input indicator, "bright" digital input is 1
4. RO0~RO3: relay output indication, "bright" relay RO and COM closure
Using the default communication parameters
When you forget module communication (ID, baud rate, parity bit), the INIT and
GND pins are short circuited, module electrifying, The communication parameters of
the module are (9600, N, 8, 1), ID is 1.INIT and GND pin is disconnected, module using
parameters set by the user, default parameters for the module (9600, N, 8, 1), ID is 1.

dadata1HTB1oLDKJHvpK1RjSZFqq6AXUVXab

Specification

Brand Name : BADODOSECURITY

+